Free practice tests for Core, Type I, Type II, Type III and Universal, with an explanation for every answer. Written by a licensed HVAC contractor with 20 years in the field.
EPA 608 practice test
Pick a section. Each practice test pulls questions in random order and shuffles the answers, so retakes stay fresh. You'll see why each answer is right as you go. Question bank: 27 Core, 10 Type I, 13 Type II, 12 Type III.
These are original practice questions built from EPA's published test topics, not questions from the official exam. Always check current rules on EPA.gov.
The four EPA 608 certification types
Everyone takes Core. Then pick the Type that matches the equipment you work on.
Core (required)
Ozone depletion, the Clean Air Act and Montreal Protocol, venting rules, recover/recycle/reclaim, refrigerant and oil basics, evacuation, cylinder safety and shipping. You must pass Core plus at least one Type.
Type I: Small appliances
Equipment manufactured, charged and hermetically sealed at the factory with 5 pounds of refrigerant or less: refrigerators, freezers, window units, PTACs, dehumidifiers, vending machines and water coolers.
Type II: High and very high pressure
Servicing or disposing of high- and very high-pressure appliances, except small appliances and motor vehicle AC. This is residential and commercial split systems, heat pumps, mini splits, rooftop units and commercial refrigeration. Most HVAC techs need this one.
Type III: Low pressure
Low-pressure appliances, mainly centrifugal chillers using refrigerants like R-123 that run below atmospheric pressure. Covers purge units, leak testing limits and chiller recovery and charging.
Universal = all of the above
Pass Core, Type I, Type II and Type III in proctored, closed-book sittings and you're certified on all equipment. If you plan to make a career of HVAC, go Universal. An open-book Type I result can't count toward Universal.
Refrigerant knowledge you need
The families, the common refrigerants, and the safety classifications that show up on the test and on the job.
CFC
Chlorofluorocarbons such as R-11 and R-12. Highest ozone depletion. Production phased out years ago.
HCFC
Hydrochlorofluorocarbons such as R-22 and R-123. Still contain chlorine, so they still deplete ozone, just less than CFCs. New R-22 production ended January 1, 2020.
HFC / HFO
R-410A, R-134a and R-32 are HFCs; R-1234yf is an HFO. No chlorine, so zero ozone depletion. HFCs are now being phased down because of global warming potential (GWP).
| Refrigerant | Type | Safety class | Where you'll see it |
|---|---|---|---|
| R-22 | HCFC | A1 | Older residential and commercial AC; service only, from recovered or reclaimed supply |
| R-410A | HFC blend (zeotropic) | A1 | Residential AC, heat pumps and mini splits; being replaced in new equipment |
| R-32 | HFC | A2L | Newer mini splits and residential systems |
| R-454B | HFO/HFC blend | A2L | Newer residential and light commercial AC and heat pumps |
| R-134a | HFC | A1 | Medium-temperature refrigeration, chillers, older auto AC |
| R-123 | HCFC | B1 | Low-pressure centrifugal chillers (Type III) |
| R-290 | Hydrocarbon (propane) | A3 | Small self-contained refrigeration and some small appliances |
Reading the safety class
The letter is toxicity: A = lower toxicity, B = higher toxicity. The number is flammability: 1 = no flame spread, 2L = lower flammability, 2 = flammable, 3 = higher flammability. A2L refrigerants like R-32 and R-454B need A2L-rated tools and the manufacturer's procedures.
Blends and oils
400-series blends are zeotropic: they have temperature glide and must be charged as liquid to avoid fractionation. 500-series blends are azeotropic and behave like one refrigerant. HFC systems use POE oil, which soaks up moisture fast, so keep it sealed.
Learn it on real jobs: HVAC Tips for Technicians
The test asks you to know it. My HVAC Tips for Technicians playlist shows you how it's done in the field: recovery, vacuum, charging, leak repair and more.
HVAC Tips for Technicians
No-fluff, real-world HVAC training from the job site, for techs, installers, apprentices and students.
Open full playlist on YouTube →How to Recover, Vacuum, and Charge a Mini Split
Recovery, vacuum and charging are on every section of the exam. Watch the whole process start to finish.
Take it to the field
Once you're certified, put the PT charts, superheat and subcooling, and diagnostics in your pocket.
AC Tool Pro
Diagnose in heating or cooling mode, PT charts, airflow and BTU calculators, and a 3D view of every component. Used by 200+ techs.
Official EPA resources
Go straight to the source for the rules, test topics and approved testing organizations.
Who's teaching this?
I'm Taddy — a licensed mechanical contractor in Tennessee with 20 years in the field. I run Fuller Heating and Cooling and the Taddy Digest YouTube channel, where 250,000+ techs, students and homeowners learn HVAC and solar from real jobs, not textbooks. I'll keep you cool if you let me.
EPA 608 questions
How many questions are on the EPA 608 exam?
Each section (Core, Type I, Type II and Type III) has 25 multiple-choice questions. Universal certification means passing all four sections, which is 100 questions.
What score do I need to pass?
You need 18 of 25 correct (72%) on each section you take, and each section is scored on its own. If Type I is taken open-book without a proctor, the passing score is higher: 84%.
Do I have to pass Core?
Yes. You must pass Core plus at least one Type section to be certified.
Does EPA 608 certification expire?
No. Section 608 technician certification does not expire.
Who gives the test and issues the card?
An EPA-approved certifying organization gives the test and issues your card. EPA itself does not issue cards.
Is this site affiliated with the EPA?
No. EPA Prep 608 is an independent study site by Taddy Digest. The practice questions are original and written to cover EPA's published test topics; they are not the official test bank.
EPA Prep 608 is an independent study resource and is not affiliated with or endorsed by the U.S. Environmental Protection Agency.